Installation Guide of 1734-AENTR

Installation Instructions

POINT I/O Dual Port EtherNet/IP

Adapter

Catalog numbers 1734-AENTR

Table of Contents

Topic

Page

Important User Information

2

Environment and Enclosure

3

Preventing Electrostatic Discharge

3

North American Hazardous Location Approval

4

European Hazardous Location Approval

4

About The Adapter

6

Before You Begin

7

Determine Compatibility

7

Understand Messaging

7

Configure Autobaud

8

Install the Adapter

8

Set the Network Address

9

Replace The Adapter

11

Wire The Adapter

13

Interpret Status Indicators

15

Specifications

17

Additional Resources

22

Rockuuell

Ailen-Bradley · Rockwelsofrtware Automaion

 

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical

equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid-State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at

http://www.rockwellautomation.com/literature/) describes some important differences between

solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell

Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death,

property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you

identify a hazard, avoid a hazard and recognize the consequences.

SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.

IMPORTANT

Identifies information that is critical for successful application and understanding of the product.

Publication 1734-IN040C-EN-P – December 2018

 

Environment and Enclosure

ATTENTION: This equipment is intended for use in a Pollution Degree 2

industrial environment, in overvoltage Category II applications (as defined in EN/IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.

This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such

environments.

This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific

environmental conditions that will be present and appropriately designed to

prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA or be approved for the application if nonmetallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings that are required to

comply with certain product safety certifications. In addition to this publication, see the following:

• Industrial Automation Wiring and Grounding Guidelines, publication 1770-IN041, for more installation requirements.

• NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.

Preventing Electrostatic Discharge

ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines

when you handle this equipment:

• Touch a grounded object to discharge potential static.

• Wear an approved grounding wriststrap.

• Do not touch connectors or pins on component boards.

• Do not touch circuit components inside the equipment.

• Use a static-safe workstation, if available.

• Store the equipment in appropriate static-safe packaging when not in use.

Publication 1734-IN040C-EN-P – December 2018

 

4 POINT I/O Dual Port EtherNet/IP Adapter

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:

Informations sur l’utilisation de cet équipement en environnements dangereux:

Products marked “CL I, DIV 2, GPA, B,C, D” are suitable for use in Class I Division 2 Groups A, B,C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate

indicating the hazardous location temperature code.

When combining products within a system, the most

adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.

Les produits marqués “CL I, DIV 2, GPA, B,C, D” ne conviennent qu’à une utilisation en environnements de Classe I Division 2 Groupes A, B,C,D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d’identification qui indiquentle code de température pour les environnements

dangereux. Lorsque plusieurs produits sont combinésdans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons

d’équipements dans le système sont sujettes à inspection par les autorités localesqualifiées au moment del’installation.

EXPLOSION HAZARD

Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

Do not disconnect connections to this equipment unless power has been

removed or the area is known to be

nonhazardous. Secure any external

connections that mate to this equipment by using screws, sliding latches,

threaded connectors, or other means provided with this product.

• Substitution of components may impair suitability for Class I, Division 2.

RISQUE D’EXPLOSION

Couper le courant ou s’assurer que

l’environnementest classé non dangereux avant dedébrancher l’équipement.

Couper le courant ou s’assurer que

l’environnementest classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l’aide devis, loquets

coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.

La substitution de composants peut rendre cet équipement inadapté à une utilisation en

environnement de Classe I, Division 2.

European Hazardous Location Approval

The following applies to products marked II 3 G:

• Are Equipment Group II, Equipment Category 3, and comply with the Essential Health and Safety Requirements relating to the design and construction of such equipment given in Annex II to Directive 2014/34/EU. See the EC Declaration of Conformity at http://www.rockwellautomation.com/products/certification for details.

• The type of protection is Ex nA IICT4 Gc according to EN 60079-15.

Comply to Standards EN 60079-0:2012+A11:2013, EN 60079-15:2010, reference certificate number DEMKO 04 ATEX 0330347X.

• Are intended for use in areas in which explosive atmospheres caused by gases,

vapors, mists, or air are unlikely to occur, or are likely to occur only infrequently and for short periods. Such locations correspond to Zone 2 classification according to ATEX directive 2014/34/EU.

Publication 1734-IN040C-EN-P – December 2018

 

ATTENTION: If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

ATTENTION: Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this

equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

ATTENTION: Installation, adjustments, putting into service, use, assembly,

disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

ATTENTION: In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not

dismantle the module.

ATTENTION: This equipment is certified for use only within the surrounding air temperature range of -20…+55 °C (-4…+131 °F). The equipment must not be used outside of this range.

ATTENTION: Use only a soft dry anti-static cloth to wipedown equipment. Do not use any cleaning agents.

WARNING: Special Conditions for Safe Use:

• This equipment is not resistant to sunlight or other sources of UV radiation.

• This equipment shall be mounted in an ATEX/IECEx Zone 2 certified

enclosure with a minimum ingress protection rating of at least IP54 (in

accordance with EN/IEC 60079-15) and used in an environment of not more than Pollution Degree 2 (as defined in EN/IEC 60664-1) when applied in

Zone 2 environments. The enclosure must be accessible only by the use of a tool.

• This equipment shall be used within its specified ratings defined by Rockwell Automation.

• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 140% of the peak rated voltage when applied in Zone 2 environments.

• The instructions in the user manualshall be observed.

• This equipment must be used only with ATEX certified Rockwell Automation backplanes.

• Earthing is accomplished through mounting of modules on rail.

• Devices shall be used in an environment of not more than Pollution Degree 2.

Publication 1734-IN040C-EN-P – December 2018

 

WARNING: Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.

WARNING: Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.

About The Adapter

Read this publication for information about the POINT I/O™ Dual Port EtherNet/IP™ adapter, a communications adapter for POINT I/Omodules.

This adapter is for the POINT I/O backplane that provides connectivity to an

EtherNet/IP network with two RJ-45 connectors for 2 port pass-through to support daisy-chain or ring, and the existing star and tree network topologies.

1734-AENTR Adapter

 

1734-AENTRPOINTIOModuleStatus

NetworkActivityNetwork StatusPointBus Status SystemPower

FieldPowerLink1Activity/Status022 34 5Link2Activity/Status6 70

1

2

3

4

 

44849

Publication 1734-IN040C-EN-P – December 2018

 

Description

Description

1

Status indicators

4

DIN rail locking screw (orange)

2

Removable Terminal Block (RTB) handle

5

Ethernet network RJ-45 connectors

3

Removable Terminal Block (RTB)

6

Node address pen push thumbwheel

Before You Begin

To effectively use your adapter, note the following considerations.

Determine Compatibility

RSLogix 5000® version 17 or greater must be used for the 1734-AENTR Add-on Profile. The 1734-AENTR adapters will accept I/O connections with the electronic keying for the 1734-AENT. This allows the 1734-AENTR adapter to be used in a daisy-chain topology with the 1734-AENT profile used for the 1734-AENTR.

If using the adapter with a 1756-ENBT module, 1768-ENBT module or anL3xE processor, use the following required firmware versions for these bridge modules:

• 1756-ENBT firmware version 4.006 or greater

• 1768-ENBT firmware version 2.003 or greater

• L3xE processor firmware version 17 or greater

If you use the BootP utility to assign IP addresses to the adapter, use version 2.3.2 or greater.

Understand Messaging

Class 3 (Explicit Message) requests through the 1734-AENTR adapter to a specific

POINT I/O module do not always receive a response from the I/O modules. In the case where the I/O module does not reply to the request, the adapter responds with an error code indicating a time-out.

Establish I/O Connections

When you start a POINT I/O system and establish I/O connections, the outputs

transition to the Idle state, applying Idle state data before going to Run mode. This occurs even when the controller making the connection is already in Run mode.

Publication 1734-IN040C-EN-P – December 2018

 

8 POINT I/O Dual Port EtherNet/IP Adapter

Configure Autobaud

The adapter cannot reconfigure anI/O module that you previously configured to operate at a fixed baud rate. When you reuse a POINT I/O module from another POINT I/O system, configure the module to autobaud before using it with the adapter.

Install the Adapter

Follow this procedure to install the adapter on the DIN rail.

1. Position the adapter vertically above the DIN rail. Make sure that the DIN rail lock is in horizontal position.

2. Press down firmly to install the adapter on aDIN rail, noting that the locking mechanism locks the adapter to the DIN rail.

3. Set the node address on the node address pen push thumbwheel. See Set the Network Address for more information on setting the IP address.

4. Slide the safety end cap up to remove it, exposing the backplane and power interconnections.

ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so

could result in equipment damage or injury from electric shock.

ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated chromate-passivated steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately. Be sure to ground the DIN rail

properly. Refer to Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1, for more information.

ATTENTION: Allow 25.4 mm (1 in.) of space between adjacent equipment for adequate ventilation.

Publication 1734-IN040C-EN-P – December 2018

 

POINT I/O Dual Port EtherNet/IP Adapter 9

ATTENTION: Do not remove or replace an Adapter Module while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.

WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

Set the Network Address

The adapter ships with the pen push thumbwheel switches set to 999 and DHCP enabled. You can set the network Internet Protocol (IP) address in the following ways:

• Use the pen push thumbwheel switches on the adapter.

• Use aDynamic Host Configuration Protocol (DHCP) server, such as Rockwell Automation BootP/DHCP.

• Retrieve the IP address from nonvolatile memory.

The adapter reads the thumbwheel switches first to determine if the switches are set to a valid number. You set the node address using the 3-position pen push thumbwheel switch using a pen tip. Press the + or – buttons with a pen tip to change the number.

Note: Press a pen tip into the center of the button cross, perpendicular to the button. You only need asmall amount of force to press the button (approximately 2N).

Valid settings range from 001…254. When you use the thumbwheel to assign an address and set it to 001, the adapter gateway address is set to 0.0.0.0. and the subnet mask is

255.255.255.0. When you use the thumbwheel to assign an address and set it between 002…254, the adapter gateway address is set to 192.168.1.1.

The adapter does not have a host name assigned, or use any Domain Name System when using the thumbwheel settings.

Publication 1734-IN040C-EN-P – December 2018

 

Network Address Thumbwheel

 

Network node address

pen push thumbwheel – Press the center of either the + or – buttons to change the number

SS

44848

 

Refer to publication POINT I/O and ArmorPOINT® I/O Dual Port EtherNet/IP Adapter User Manual, 1734-UM017 for more information.

If you set the switches to an invalid number (for example, 000 or avalue greater than 254 excluding 888), the adapter checks to see if you enabled DHCP.

DHCP Enabled and Not Enabled

DHCP State

Adapter Action

Enabled

Asks for an address from a DHCP server. The DHCP server also assigns other Transport Control Protocol (TCP) parameters.

Not enabled

Uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory.

WARNING: When you change switch settings while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

Publication 1734-IN040C-EN-P – December 2018

 

Replace The Adapter

Use these procedures to install a replacement adapter to an existing system.

1. Disconnect the Ethernet connector(s) from the adapter.

2. Pull upon the Removable Terminal Block (RTB) handle to remove the terminal block.

WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous

location installations.

Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the

module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

WARNING: When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

3. Remove the adjacent module from its base.

4. Use a small bladed screwdriver to rotate the DIN rail locking screw to a vertical position. This releases the locking mechanism.

5. Lift straight up to remove.

6. Slide the safety end cap up to remove it, which exposes the backplane and power connections.

7. Position the replacement adapter vertically above the DIN rail, making certain the DIN rail lock is in the horizontal position.

8. Slide the adapter down, allowing the interlocking side pieces to engage the adjacent module.

Publication 1734-IN040C-EN-P – December 2018

 

9. Press firmly to seat the adapter on the DIN rail, noting that the adapter locking mechanism will snap into place.

10. Set the node address on the Node Address pen push thumbwheel using a pen tip.

TIP Press a pen tip into the center of the button cross, perpendicular to the button. You only need a small amount of force to press the button (approximately 2N).

11. Insert the end of the terminal block opposite the handle into the base unit, noting that this end has a curved section that engages with the wiring base.

12. Rotate the terminal block into the wiring base until it locks itself into place.

13. Replace the adjacent module in its base.

14. Reconnect the Ethernet cable(s) to the adapter.

15. Set the IP Address for this module.

16. Configure the adapter’s chassis size.

Publication 1734-IN040C-EN-P – December 2018

 

Wire The Adapter

1734-AENTR

Module

Status

Network

Activity

Network

Status

Status

System Power

Field Power

Ethernet RJ-45

connectors

NC

Chas Gnd

Link 2

C

V

 

NC = No Connection

Chas GND = Chassis Ground

C = Common V = Supply

4

C

6

V

1 NC

3 Chas Gnd

5 C

7 V

 

IP ADDRESS44848

IMPORTANT Do not connect 120/240VAC power to this supply. This DC supply will be

connected to the internal power bus.

Publication 1734-IN040C-EN-P – December 2018

 

14 POINT I/O Dual Port EtherNet/IP Adapter

WARNING: When used in a Class I, Division 2, hazardous location, this

equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.

WARNING: If you connect or disconnect wiring while the field-side power is

on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is

nonhazardous before proceeding.

WARNING: Do not wire more than two conductors on any single terminal.

WARNING: To comply with the CE Low Voltage Directive (LVD),this equipment must be powered from a Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV) compliant source.

Publication 1734-IN040C-EN-P – December 2018

 

Interpret Status Indicators

Refer to the following diagram and table for information on how to interpret the status indicators.

Status Indicators

 

Link 1 activity/ status

Link 2 activity/ status

IP ADDRESS

Module status Network activity Network status POINTBus status System power

Field power

43264

 

Indicator Status for Modules

Indicator

Status

Description

Module status

Off

No power applied to device

Flashing green

Device needs commissioning due to missing, incomplete, or incorrect configuration.

Solid green

Device operating normally

Flashing red

Recoverable fault.

Complete firmware update, verify address switches.

Solid red

Unrecoverable fault, may require device replacement

Flashing red/green

Module self-test

Publication 1734-IN040C-EN-P – December 2018

 

Indicator Status for Modules

Indicator

Status

Description

Network activity

Off

No link established with Port 1 or Port 2.

Flashing green

Transmit or receive activity present on Port 1 and/or Port 2 @ 100 Mb.

Transmit or receive activity present on Port 1 and/or Port 2. One port @ 100 Mb and the other port @ 10 Mb.

Solid green

Link established with Port 1 and/or Port 2 @ 100 Mb. Link established with Port 1 and Port 2.

One port @ 100 Mb and the other port @ 10 Mb.

Solid yellow

Link established with Port 1 and/or Port 2 @ 10 Mb.

Network status

Off

Device is not on-line

– Device has not completed dup_MAC_id test.

– Device not powered – check module status indicator

Flashing green

Device is on-line but has no CIP connections in the established state.

Solid green

Device on-line and has CIP connections in the established state.

Flashing red

One or more CIP connections in timed-out state. Check for I/O module failure and controller operation.

Note: This does not apply to POINTGuard I/O connection timeout.

Solid red

Duplicate IP address detected.

Verify IP address setting and correct, as needed.

Flashing red/green

Module self-test

POINTBus status

Off

Device is not online.

– Device has not completed Dup_MAC_ID test.

– Device not powered – check module status indicator.

Flashing green

Device is online but has no connections in the established state. Firmware (NVS) update in progress.

Solid green

Adapter online with connections established.

Flashing red

Recoverable fault occurred:

At cycle power, the number of expected modules does not equal the number of modules present.

A module is missing.

Nodefault (I/O connection timeout) occurred.

Solid red

Unrecoverable fault occurred – thse adapter is bus off.

Flashing red/green

LED powerup testis in progress.

System power

Off

Not active. Adapter power is off or there is a DC-DC converter problem.

Solid green

System power is on. DC-DC converter output is active (5V).

Field power

Off

Not active. Adapter power is off.

Solid green

Power is on. 24V input is present.

Publication 1734-IN040C-EN-P – December 2018

 

Indicator Status for Modules

Indicator

Status

Description

Link 1 or Link 2 activity / status

Off

No link established.

Solid green

Link established @ 100 Mbps.

Flashing green

Transmit or receive activity present on indicated port @ 100 Mbps.

Solid yellow

Link established @ 10 Mbps.

Flashing yellow

Transmit or receive activity present on indicated port @ 10 Mbps.

Specifications

POINT I/O EtherNet/IP Adapter — 1734-AENTR

Attribute

Value

Expansion I/O capacity, max

•63 modules

• Up to 5 rack-optimization (for digital modules only) and/or

enhanced rack-optimization (for digital, analog, and specialty modules) connections

• 31 direct connections(1)

• 1734-AENTR, 1734-AENTRK backplane current output = 0.8 A.

• Actual number of modules can vary.

• Add up current requirements of modules you want to use to make sure they do not exceed the amperage limit of 0.8 A for the 1734-AENTR or 1734-AENTRK adapter.

• Backplane current can be extended beyond 0.8 A by

1734-EP24DC or 1734-EPAC backplane extension power supplies.

• Add multiple 1734-EP24DC or 1734-EPAC modules to reach the 63 module max.

POINTBus current requirements, max

• 50 mA (Catalog number 1734-IB4D)

• 75 mA (Catalog numbers 1734-IB2, 1734-IB4, 1734-IB8,

1734-IV2, 1734-IV4, 1734-OB2, 1734-OB4, 1734-OB8,

1734-OB2E, 1734-OB2EP, 1734-OB4E, 1734-OB8E, 1734-OV2E, 1734-OV4E, 1734-232ASC, 1734-485ASC, 1734-ARM,

1734-IV8, 1734-OV8E, 1734-IE4C, 1734-IE8C, 1734-OE4C, 1734-IA4, 1734-IM4, 1734-OA4, 1734-IR2E, 1734-IE2C,

1734-OE2C, 1734-IE2V, 1734-OE2V, 1734-IA2, 1734-IM2, 1734-OA2)

• 80 mA (Catalog numbers 1734-OW2, 1734-OW4)

• 100 mA (Catalog numbers 1734-OX2, 1734-8CFG, 1734-8CFGDLX, 1734-4IOL)

• 110 mA (Catalog number 1734-SSI)

• 160 mA (Catalog numbers 1734-IJ2, 1734-IK2)

• 175 mA (Catalog number 1734-IT2I)

• 180 mA (Catalog numbers 1734-VHSC5, 1734-VHSC24)

• 220 mA (Catalog numbers 1734-IR2, 1734-IR2E)

Module location

Starter module – left side of the 1734 system

(1) Maximum 31 direct connections for standard I/O or maximum 20 direct connections if any safety I/O module resides in the backplane.

Publication 1734-IN040C-EN-P – December 2018

 

Power Supply

Attribute

Value

Input voltage rating

24V DC @ 10A

Input voltage, range

10…28.8V DC

Field side power, max

24V DC @ 400 mA

Inrush current, max

6 A for 10 ms

Input overvoltage protection

Reverse polarity protected

POINTBus output current, max

5V DC @ 0.8A

Interruption

Output voltage stays within specifications when input drops out for 10 ms @ 10V with max load

Ethernet Communication

Attribute

Value

Ethernet communication rate

10/100 Mbits/s, half or full-duplex

Ethernet ports

2, configured as Embedded Switch

Ethernet network topologies supported

Star, Tree, Daisy-chain/Linear, and Ring

Ethernet connectors

RJ-45, Category 5

Ethernet cable

Category 5:

shielded or unshielded

Ethernet wire connections, max

See Wire Size on page 19

General Specifications

Attribute

Value

Indicators

3 red/green status indicators on CPU:

– Module status

– Network status (Ports 1 and 2 combined)

– POINTBus status

1 green/yellow status indicator on CPU:

– Network activity (Ports 1 and 2 combined)

2 green/yellow status indicators on base:

– Link 1 activity/status

– Link 2 activity/status

2 green power supply status indicators on DC-DC Converter:

– System power (5V DC to POINTBus Out)

– Field power (24V DC from Field In)

Power consumption, max

10.4 W @ 28.8V DC

Power dissipation, max

6.3 W @ 28.8V DC

Publication 1734-IN040C-EN-P – December 2018

 

General Specifications

Attribute

Value

Input overvoltage protection

Reverse polarity protected

Thermal dissipation, max

21.5 BTU/hr @ 28.8V DC

Isolation voltage

50V (continuous), Reinforced Insulation Type, between all circuits

Type tested @ 500VAC for 60 s

Field power supply

10…28.8V DC @ 10A

Field power output

10…28.8V DC @ 9A

Module input

10…28V DC @ 1000 mA

POINTBus output, max

5V DC @ 0.8A

Dimensions (HxWxD), approx.

76.2 x 73.0 x 133.4 mm (3.0 x 2.87 x 5.25 in.)

Enclosure type rating

None (open-style)

Terminal base screw torque

0.8 Nm (7 lb-in)

Weight, approx.

0.28 Kg (0.62 lb)

Wiring category(1) (2)

1 – on power ports

1 – on communications ports

Wire Size

Power connections:

0.34… 2.1 mm2 (22…14 AWG) solid or stranded copper wire rated @ 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max or

90 °C (194 °F) for ControlLogix. Ethernet wiring:

RJ45 connector according to IEC 60603-7, 2 or 4 pair Category 5e min cable according to TIA 568-B.1 or Category 5 cable according to ISO/IEC 24702.

North American temp code

T4

ATEXTemp Code

T4

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-IN041.

(2) Use this Conductor Category information for planning conductor routing as described in the appropriate System Level Installation Manual.

At the end of its life, this equipment should be collected separately from any unsorted municipal waste.

Publication 1734-IN040C-EN-P – December 2018

 

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock): –20…55 °C (-4…131 °F)

Temperature, surrounding air, max

55 °C (131 °F)

Temperature, nonoperating

IEC60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)

IEC60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)

IEC60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5 g @ 10…500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Emissions

IEC 61000-6-4

ESD immunity

IEC61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz

10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz

10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:

±4 kV @ 5 kHz on power ports

±3 kV @ 5 kHz on communications ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports ±2 kV line-earth (CM) on communications ports

Conducted RF immunity

IEC61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Publication 1734-IN040C-EN-P – December 2018

 

Certifications

Certification (when product is marked)(1)

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CE

European Union 2014/30/EU EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity

EN 61000-6-4; Industrial Emissions

EN 61131-2; Programmable Controllers (Clause 8,Zone A & B)

European Union 2011/65/Eu RoHS, compliant with: EN 50581; Technical Documentation

RCM

Australian Radiocommunications Act, compliant with: AS/NZS CISPR11; Industrial Emissions

Ex

European Union 2014/34/EU ATEX Directive, compliant with: EN 60079-0:2012 + A11:2013; General Requirements

EN 60079-15:2010; Potentially Explosive Atmospheres, Protection “n” II 3 G Ex nA IICT4 Gc

DEMKO 04 ATEX 0330347X

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with:

Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation

EtherNet/IP

ODVA conformance tested to EtherNet/IP specifications

(1) See the Product Certification link at http://www.rockwellautomation.com/global/certification/overview.page for Declaration of Conformity, Certificates, and other certification details.

Publication 1734-IN040C-EN-P – December 2018

 

Additional Resources

Refer to these related publications, as needed.

Resource

Description

1734 POINT I/O and 1738 ArmorPOINT

I/O Dual Port EtherNet/IP Adapter User Manual, publication

1734-UM017.

A detailed description of module functionality, configuration, installation procedure and information on how to use the POINT I/O and ArmorPOINT I/O Dual Port EtherNet/IP adapters.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-IN041.

More information on proper wiring and grounding techniques.

If you would like a manual, you can:

• download a free electronic version from the internet:

http://www.rockwellautomation.com/literature/

• purchase a printed manual by contacting your local Allen-Bradley distributor or Rockwell Automation representative.

Publication 1734-IN040C-EN-P – December 2018

 

Notes:

Publication 1734-IN040C-EN-P – December 2018

 

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At

http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell

Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance

If you experience a problem within the first 24 hours of installation, please review the information that’s contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.

United States or Canada

1.440.646.3434

Outside United States or Canada

Use the Worldwide Locator at

http://www.rockwellautomation.com/support/americas/phone_en.html, or

contact your local Rockwell Automation representative.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

United States

Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback

Your comments will help us serve your documentation needs better. If you have any suggestions on how to

improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Automation maintains current product environmental information on its website at

http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, ArmorPOINT, POINT I/O, Rockwell Automation, Rockwell Software, RSLogix 5000, and TechConnect are trademarks of Rockwell Automation, Inc.

EtherNet/IP isa trademark of ODVA, Inc.

Trademarks not belonging to Rockwell Automation are property of theirrespective companies.

Rockwe otomasyon TicaretA · §,kar plaza iyMerkeziE Blok kat:634752iserenky, istanbul, Tel: +90 (216) 5698400

power, control and Information solutions Headquarters

Americas: Rockwell Automation, 1201 south second street, Milwaukee, WI 53204- 2496USA, Tel: (1)414. 382. 2000, Fax: (1)414. 382.4444

Europe/Middle East/Africa: Rockwell Automation NV, pegasus park, Dekleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2663 0600, Fax: (32) 2663 0640 Asia pacihc: Rockwell Automation, Level 14, core F, cyberport 3, 100 cyberport Road, Hongkong, Tel: (852) 28874788, Fax: (852) 2508 1846

Publication 1734-IN040C-EN-P – December 2018

Supersedes Publication 1734-IN040B-EN-P December 2009 Copyright © 2018 Rockwell Automation, Inc. All rights reserved.ll 